Technical data of safety analog inputsPermalink

This is the web edition of the original ‎⮫ AC500-S safety user manual, version 1.3.2. This web edition is provided for quick reference only. The original safety user manual must be used to meet functional safety application requirements.

DANGER

DANGER
DANGER
DANGER

DANGER

DANGER

Exceeding the permitted process or supply voltage range (< -35 V DC or > +35 V DC) could lead to unrecoverable damage of the system.

Bilgi

Değer

Birim

Number of channels per module

4

 

Configurability, 1 channel mode

0 ... 20

mA

Configurability, 1 channel mode

4 ... 20

mA

Configurability, 2 channel mode

4 ... 20

mA

Channel input resistance, in active mode

~ 125

Ω

Channel input resistance, in inactive mode

~ 15

kΩ

Distribution of channels into groups

2 groups of 2 channels each.

Bilgi

Değer

Birim

Time constant of the input filter

1

ms

Conversion cycle

0.33

ms

Resolution

14

bits

Temperature coefficient ± % of full scale (0 ... 20 mA)

±0.005

%/K

Maximum error at +25 °C ± % of full scale (0 ... 20 mA)

± 0.25

%

Maximum error over full temperature range ± % of full scale (0 ... 20 mA)

± 0.25

%

Value of a LSB (least significant bit)

2.03

µA

Maximum permanent allowed overload (no damage) (self-protected), voltage

32

V DC

Maximum permanent allowed overload (no damage) (self-protected), current

24

mA

Non-linearity (of full scale)

±0.05

%

Sample repetition time

3.3

ms

Input filter characteristics - first order, filter time constant

1

ms

Transition frequency

160

Hz

Overvoltage protection

Yes

 

Electrical isolation

Against internal supply and other modules.

Input signal indication

One LED per channel.

Maximum temporary deviation during specified electrical interference test ± % of full scale

Bilgi

Değer

Birim

Deviation during radiated and conducted disturbance

< 0.1

%

Deviation during burst test

max. 0.33

%

Deviation during surge test

up to 50

%

Deviation during electrostatic discharge

no deviation

 

Analog input protection

Bilgi

Değer

Type of analog input protection

suppressor diode

Cable length

Bilgi

Değer

Birim

Max. cable length, shielded

100

m